MEDIA FOR WHICH DESIGNED | REFRIGERANT 12 |
WATER FOR WHICH DESIGNED | FRESH |
WATER CONNECTION QUANTITY | 2 |
WATER CONNECTION TYPE | FLANGE |
WATER CONNECTION SIZE | 2-1/2 IN. N STD |
WATER SIDE TEST MINIMUM PRESSURE | 225.0 POUNDS PER SQUARE INCH |
REFRIGERANT OPERATING LOCATION | IN TUBES |
MOUNTING POSITION | HORIZONTAL |
EFFECTIVE COOLING AREA | 169.000 SQUARE FEET |
TUBE TYPE | STRAIGHT |
TUBE MATERIAL | COPPER |
SHELL MATERIAL | BRASS |
SHELL LENGTH | 6.500 FEET |
SHELL OUTSIDE DIAMETER | 12.875 INCHES |
REFRIGERANT INLET CONNECTION QUANTITY | 1 |
REFRIGERANT INLET CONNECTION TYPE | TUBE |
REFRIGERANT INLET CONNECTION SIZE | 1-5/8 IN. |
REFRIGERANT OUTLET CONNECTION QUANTITY | 2 |
REFRIGERANT OUTLET CONNECTION TYPE | TUBE |
REFRIGERANT OUTLET CONNECTION SIZE | 2-5/8 IN. |
REFRIGERANT SIDE TEST MINIMUM PRESSURE | 225.0 POUNDS PER SQUARE INCH |
OVERALL LENGTH | 89.000 INCHES NOMINAL |
OVERALL WIDTH | 16.875 INCHES NOMINAL |
REFERENCE NUMBER DIFFERENTIATING CHARACTERISTICS | FOR25 TON NONMAGNETIC AIR CONDITIONING PLANT |
THE MANUFACTURERS DATA | |
MANUFACTURERS CODE | 10855 |
DESIGN CONTROL REFERENCE | 10M28-704 |