ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
BODY LENGTH | 2.500 INCHES NOMINAL |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
BODY WIDTH | 1.500 INCHES NOMINAL |
BOSS HEIGHT | 0.125 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.935 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.062 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP W/AUXILIARY LOAD TERMINAL ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
MATERIAL | PLASTIC CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.359 INCHES NOMINAL |
NOMINAL THREAD SIZE | 0.138 INCHES |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 230.0 AC ALL LOCATIONS |
POLE QUANTITY | 2 |
RESET METHOD | MANUAL |
TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
THREAD QUANTITY PER INCH | 32 |
THREAD SERIES DESIGNATOR | UNC |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.250 MINIMUM AT 200 PCT AND 0.800 MAXIMUM AT 200 PCT ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
ULTIMATE TRIP TIME PER POLE IN SECONDS | 1.010 MINIMUM AND 5.450 MAXIMUM ALL LOCATIONS |