5920-00-066-6885 ARRESTER,LIGHTNING Index 5998-00-066-6888 CIRCUIT CARD ASSEMBLY

National Stock Number:
5925-00-066-6887

Federal Supply Class:
5925

National Item Identification Number:
000666887

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
48A8101G479500WESTINGHOUSE ELECTRIC CORP
48A8101G489946EATON CORPORATION


Techincal Specification:
POLE QUANTITY2
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE100.0 AMPERES AC AND
10000.0 AMPERES DC ALL LOCATIONS
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY4 COMPRESSION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS600.0 AC AND
250.0 DC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND
TIME DELAY ALL LOCATIONS
RESET METHODMANUAL
MOUNTING FACILITY TYPE AND QUANTITY4 UNTHREADED HOLE
CASE MATERIALPLASTIC
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS15000.0 AC AND
15000.0 DC ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING25.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT300.000 MINIMUM AT 150 PCT AND
1400.000 MAXIMUM AT 150 PCT AND
100.000 MINIMUM AT 200 PCT AND
400.000 MAXIMUM AT 200 PCT AND
30.000 MINIMUM AT 300 PCT AND
100.000 MAXIMUM AT 300 PCT AND
16.000 MINIMUM AT 400 PCT AND
55.000 MAXIMUM AT 400 PCT AND
10.000 MINIMUM AT 500 PCT AND
35.000 MAXIMUM AT 500 PCT AND
0.040 MINIMUM AT 1000 PCT AND
10.000 MAXIMUM AT 1000 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT117.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OVERALL LENGTH10.180 INCHES NOMINAL
OVERALL HEIGHT8.250 INCHES NOMINAL
OVERALL WIDTH5.500 INCHES NOMINAL
NOMINAL THREAD SIZE0.312 INCHES
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
ACTUATOR FUNCTIONTRIP W/SEPARATE RESET
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF
FEATURES PROVIDEDADJUSTABLE TRIP RELEASE
ARC QUENCHING METHODDEION
PRECIOUS MATERIALSILVER
SPECIAL FEATURESMTG HOLES ON 7.250 IN. BY 2.750 IN. MTG CENTERS