5910-00-080-9280 CAPACITOR,FIXED,MICA DIELECTRIC Index 5305-00-080-9285 SCREW,MACHINE

National Stock Number:
5925-00-080-9284

Federal Supply Class:
5925

National Item Identification Number:
000809284

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
5352950B6S1INTERNATIONAL BUSINESS MACHINES CORP PARTS ORDER CENTER DEPT E - 54
53529530874INTERNATIONAL BUSINESS MACHINES CORPORATION
53529588360INTERNATIONAL BUSINESS MACHINES CORP ENDICOTT DEVELOPMENT LAB
CCPBA1452090TELEMECANIQUE INC
CCPBA1456365SCHNEIDER ELECTRIC USA, INC.


Techincal Specification:
ACTUATOR FUNCTIONTRIP W/SEPARATE RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
BODY STYLESINGLE POLE TYPE
BOSS HEIGHT0.120 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.340 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.000 INCHES NOMINAL
FREQUENCY IN HERTZ400.0 SINGLE LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP W/DUAL RATING SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 PUSH BUTTON
OVERALL LENGTH1.969 INCHES NOMINAL
OVERALL WIDTH0.993 INCHES NOMINAL
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE4.0 AMPERES AC AND 4.0 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS200.0 AC AND 200.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY2 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE1.910 INCHES NOMINAL
NOMINAL THREAD SIZE0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS230.0 AC AND 120.0 DC SINGLE LOCATION
POLE QUANTITY1
RESET METHODMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS3.0 AC AND 3.0 DC
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
SWITCH TERMINAL TYPESCREW
SWITCH VOLTAGE RATING AND TYPE IN VOLTS115.0 AC AND 50.0 DC
TERMINAL TYPE AND QUANTITY3 EYELET
THREAD QUANTITY PER INCH32
THREAD SERIES DESIGNATORUNC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT23.000 MINIMUM AT 200 PCT AND 4.400 MAXIMUM AT 300 PCT SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING24.0 CELSIUS NOMINAL SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODTHERMAL SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT135.0 SINGLE LOCATION


Click here to Register for Free 30-day Trial