5925-00-089-0536 CIRCUIT BREAKER Index 5365-00-089-0543 SPACER,SLEEVE

National Stock Number:
5925-00-089-0537

Federal Supply Class:
5925

National Item Identification Number:
000890537

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
2601D45G0789946EATON CORPORATION
565B159G1993201GENERAL ELECTRIC CO COMPONENT PRODUCTS DIVISION OF INDUSTRIAL COMPONENTS AND MATERIALS GROUP


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
BODY HEIGHT3.700 INCHES NOMINAL
BODY LENGTH4.230 INCHES NOMINAL
BODY STYLESINGLE POLE TYPE
BODY WIDTH0.970 INCHES NOMINAL
BOSS HEIGHT0.188 INCHES NOMINAL
CASE MATERIALPLASTIC
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 SINGLE LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS300.0 AC AND 125.0 DC SINGLE LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE35.0 AMPERES AC AND 35.0 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS2500.0 AC AND 2500.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY1 SLOT
MOUNTING SLOT WIDTH0.218 INCHES NOMINAL
POLE QUANTITY1
RESET METHODMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS5.0 AC AND 5.0 DC
SWITCH LOCATION AND POSITION DESIGNATIONEXTERNAL AT POLE ONE
SWITCH TERMINAL TYPETAB, SOLDER LUG
SWITCH VOLTAGE RATING AND TYPE IN VOLTS250.0 AC AND 30.0 DC
TERMINAL TYPE AND QUANTITY1 BUS BAR AND 1 SCREW
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT10.000 MINIMUM AT 200 PCT AND 100.000 MAXIMUM AT 200 PCT SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING50.0 CELSIUS MAXIMUM SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODTHERMAL SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0 SINGLE LOCATION