ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
CASE MATERIAL | PLASTIC |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC ALL LOCATIONS |
OVERALL HEIGHT | 2.000 INCHES NOMINAL |
OVERALL LENGTH | 2.875 INCHES NOMINAL |
OVERALL WIDTH | 2.375 INCHES NOMINAL |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 35.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
NOMINAL THREAD SIZE | 0.138 INCHES |
POLE QUANTITY | 2 |
RESET METHOD | MANUAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 4 COMPRESSION |
THREAD SERIES DESIGNATOR | UNC |
THREAD QUANTITY PER INCH | 32 |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 36.000 NOMINAL AT 150 PCT ALL LOCATIONS |
TRIP RELEASE AMBIENT TEMP RATING | 25.0 CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 110.0 ALL LOCATIONS |