6625-00-089-5589 METER,AUDIO LEVEL Index 5340-00-089-5602 CONNECTOR,ROD END

National Stock Number:
5925-00-089-5596

Federal Supply Class:
5925

National Item Identification Number:
000895596

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
20A00-005716630LIMCO AIREPAIR INC.


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
BODY STYLERECTANGULAR DIMENSIONAL ENVELOPE
CASE MATERIALPLASTIC
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC ALL LOCATIONS
OVERALL HEIGHT1.530 INCHES NOMINAL
OVERALL LENGTH3.330 INCHES NOMINAL
OVERALL WIDTH2.530 INCHES NOMINAL
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE50.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 THREADED HOLE
NOMINAL THREAD SIZE0.138 INCHES
POLE QUANTITY2
RESET METHODMANUAL
TERMINAL TYPE AND QUANTITY4 THREADED STUD
THREAD SERIES DESIGNATORUNC
THREAD QUANTITY PER INCH32
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT7.000 MINIMUM AT 150 PCT AND 31.000 MAXIMUM AT 150 PCT AND 1.500 MINIMUM AT 300 PCT AND 4.000 MAXIMUM AT 300 PCT AND 0.600 MINIMUM AT 325 PCT AND 2.000 MAXIMUM AT 325 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS