ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE TWO |
BODY HEIGHT | 2.340 INCHES MINIMUM AND 2.400 INCHES MAXIMUM |
BODY LENGTH | 2.250 INCHES MAXIMUM |
BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
BODY WIDTH | 2.189 INCHES MAXIMUM |
BUSHING LENGTH | 0.235 INCHES MINIMUM AND 0.250 INCHES MAXIMUM |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.161 INCHES MINIMUM AND 1.220 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.720 INCHES MINIMUM AND 0.780 INCHES MAXIMUM |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.470 INCHES MINIMUM AND 1.530 INCHES MAXIMUM |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.720 INCHES MINIMUM AND 0.780 INCHES MAXIMUM |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH-PULL |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC ALL LOCATIONS |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 25.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 6000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
NOMINAL THREAD SIZE | 0.138 INCHES |
POLE QUANTITY | 3 |
RESET METHOD | MANUAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 6 TAB W/SCREW |
TEST DATA DOCUMENT | 98897-STSVC004 DRAWING (THIS IS THE BASIC GOVERNING DRAWING, SUCH AS A CONTRACTOR DRAWING, ORIGINAL EQUIPMENT MANUFACTURER DRAWING, ETC.; EXCLUDES ANY SPECIFICATION, STANDARD OR OTHER DOCUMENT THAT MAY BE REFERENCED IN A BASIC GOVERNING DRAWING) |
THREAD SERIES DESIGNATOR | UNC |
THREAD QUANTITY PER INCH | 32 |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 15.000 MINIMUM AT 200 PCT AND 65.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
TRIP RELEASE AMBIENT TEMP RATING | 25.0 CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 138.0 ALL LOCATIONS |
UNPACKAGED UNIT WEIGHT | 3.250 OUNCES NOMINAL |