5925-00-103-5156 CIRCUIT BREAKER Index 5925-00-103-5158 CIRCUIT BREAKER

National Stock Number:
5925-00-103-5157

Federal Supply Class:
5925

National Item Identification Number:
001035157

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
QNPL2030V11660WESTINGHOUSE ELECTRIC CORP CONTROL BUSINESS UNIT


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
BODY HEIGHT3.375 INCHES NOMINAL
BODY LENGTH3.016 INCHES NOMINAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH2.000 INCHES MAXIMUM
BOSS HEIGHT0.187 INCHES NOMINAL
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.000 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ50.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS120.0 AC ALL LOCATIONS
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE30.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS5000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY2 SLOT
MOUNTING SLOT WIDTH0.562 INCHES NOMINAL
POLE QUANTITY2
RESET METHODMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY2 CLIP AND 2 SCREW
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT40.000 MINIMUM AT 150 PCT AND 500.000 MAXIMUM AT 150 PCT ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING50.0 CELSIUS MAXIMUM ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS


Click here to Register for Free 30-day Trial