CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
72-242-1MG674193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
AM336MG674193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
ARC QUENCHING METHODMAGNETIC BLOWOUT
BODY LENGTH2.500 INCHES NOMINAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH2.250 INCHES NOMINAL
BOSS HEIGHT0.140 INCHES NOMINAL
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.938 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.750 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.062 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.750 INCHES NOMINAL
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 FIRST LOCATION
FREQUENCY IN HERTZ60.0 SECOND LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY3 TOGGLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS115.0 DC THIRD LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC FIRST LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC SECOND LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE40.0 AMPERES AC FIRST LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE40.0 AMPERES AC SECOND LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC FIRST LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC SECOND LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS2000.0 DC THIRD LOCATION
MOUNTING FACILITY TYPE AND QUANTITY6 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE2.549 INCHES MINIMUM AND 2.673 INCHES MAXIMUM
NOMINAL THREAD SIZE0.138 INCHES
POLE QUANTITY3
RESET METHODMANUAL
SPECIAL HANDLING FEATUREMAGNETIC
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 THREADED STUD
THREAD SERIES DESIGNATORUNC
THREAD QUANTITY PER INCH32
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT3.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT SECOND LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT3.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT FIRST LOCATION
TRIP RELEASE CHARACTERISTICINSTANTANEOUS THIRD LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY FIRST LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SECOND LOCATION
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
UNPACKAGED UNIT WEIGHT0.875 POUNDS NOMINAL