| ACTUATOR FUNCTION | TRIP-RESET | 
| ACTUATOR POSITION DESIGNATION | AT POLE TWO | 
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT | 
| BODY HEIGHT | 1.381 INCHES MAXIMUM | 
| BODY LENGTH | 0.781 INCHES MAXIMUM | 
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE | 
| BODY WIDTH | 1.840 INCHES MAXIMUM | 
| BUSHING LENGTH | 0.219 INCHES MINIMUM AND 0.781 INCHES MAXIMUM | 
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.469 INCHES MINIMUM AND 0.531 INCHES MAXIMUM | 
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.593 INCHES MINIMUM AND 0.655 INCHES MAXIMUM | 
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS | 
| FRAGILITY FACTOR | MODERATELY RUGGED | 
| FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS | 
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCK RESISTANT AND VIBRATION RESISTANT | 
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS | 
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE | 
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH-PULL | 
| MATERIAL | PLASTIC CASE | 
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 1.0 AMPERES AC ALL LOCATIONS | 
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 AC ALL LOCATIONS | 
| MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING WITH PANEL SEAL | 
| NOMINAL THREAD SIZE | 0.438 INCHES | 
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 200.0 AC ALL LOCATIONS | 
| SPECIAL FEATURES | AUXILIARY CONTACTS ARE CAPABLE OF CARRING 0.5 AMPERE LAMP LOAD 28 VOLDS DC | 
| POLE QUANTITY | 3 | 
| RESET METHOD | MANUAL | 
| SPECIFICATION/STANDARD DATA | 96906-MS14154 GOVERNMENT SPECIFICATION | 
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE | 
| TERMINAL TYPE AND QUANTITY | 6 TAB W/SCREW | 
| TEST DATA DOCUMENT | 81349-MIL-C-5809 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). | 
| THREAD QUANTITY PER INCH | 32 | 
| THREAD SERIES DESIGNATOR | UN | 
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 4.000 MINIMUM AT 200 PCT  AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS | 
| TRIP RELEASE AMBIENT TEMP RATING | 25.0 CELSIUS NOMINAL ALL LOCATIONS | 
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS | 
| TRIP RELEASE METHOD | THERMAL ALL LOCATIONS | 
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 145.0 ALL LOCATIONS |